Type: | Self-Starting Diesel Generator |
---|---|
Installation Method: | Portable |
Stroke: | Four Stroke |
Cooling Method: | Water Cooling |
Output Type: | AC Three Phase |
Speed: | 1500rpm |
Customization: |
---|
Suppliers with verified business licenses
Diesel Generator Set Data | ||
Manufacturer: | Jiangsu Starlight Electricity Equipment Co.,Ltd | |
Set Type: | XG-300GF | |
Prime power: | 300KW/375KVA | |
Rated Current: | 491(A) | |
Rated Frequency: | 50(Hz) | |
Start-up time: | 5~6(s) | |
Power Factor: | 0.8(Lag) | |
Rated Voltage: | 400/230(V) | |
Standard Features | ||
| |
Diesel Engine Data | ||
Manufacturer: | PERKINS | |
Model: | 2206C-E13TAG2 | |
Standby/Prime Power: | 334KW/304KW | |
Rated Speed: | 1500(r/min) | |
Cycle: | 4 stroke | |
Cylinder Arrangement: | 6in line | |
Displacement: | 14.6L | |
Bore and Stroke: | 130*157(mm) | |
Compression Ratio: | 16.3:1 | |
Governor Type: | Electronic | |
Start battery voltage: | 24V DC | |
Air Intake System | ||
Air Intake System: | Turbo | |
Max Intake Restriction: | ||
Burning Capacity: | 29 m³/min | |
Air Flow: | 428m³/min | |
Exhaust System | ||
Exhaust Gas Flow: | 70.02 m³/min | |
Exhaust Temperature: | 449ºC | |
Max Back Pressure: | 10.2kpa | |
Fuel System | ||
Fuel System: | Direct injection | |
100%( Prime Power) Load: | 201g/kwh | |
50%( Prime Power) Load: | 216g/kwh | |
Oil System | ||
Total Oil Capacity: | 40L | |
Oil Consumption: | ||
Engine Oil Tank Capacity: | ||
Oil Pressure at Rated RPM: | ||
| ||
Cooling System | ||
Cooling Way: | Water-cooled | |
Total Coolant Capacity: | 47L | |
Thermostat: | ||
Max Water Temperature: | ||
Alternator Data | ||
Manufacturer: | STARLIGHT STAMFORD/ SIEMENS/ MARATHON/ ENGGA/ KEPU | |
Excitation Mode: | Brushless and self- exciting | |
Number of phase and Access Act: | 3-phase 4-wire | |
Connecting Type: | "Y" type connecting | |
Alternator Capacity: | 375KVA | |
Alternator Efficiencies: | 95% | |
Overload: | (PRP)110% load can run 1h | |
Protection Level: | IP22-IP23 | |
Insulation Class, Temperature Rise: | H/H | |
Telephone Influence Factor (TIF): | <50 | |
THF: | <2% | |
Voltage Regulation, Steady State: | ≤±1% | |
Air Cooling Flow: | 0.216m3/s | |
Altitude: | ≤1000m | |
| ||
Genset Electrical Performance | ||
Voltage Regulation: | ≥±5% | |
Voltage Regulation, Stead State: | ≤±1% | |
Sudden Voltage Warp (100% Sudden Reduce): | ≤+25% | |
Sudden Voltage Warp (Sudden Increase): | ≤-20% | |
Voltage Stable Time (100% Sudden Reduce): | ≤6S | |
Voltage Stable Time (Sudden Increase): | ≤6S | |
Frequency Regulation, Stead State: | ≤5% | |
Frequency Waving: | ≤1.5% | |
Sudden Frequency Warp (100% SuddenReduce): | ≤+12% | |
Sudden Frequency Warp (Sudden Increase): | ≤-10% | |
FrequencyRecoveryTime(100%SuddenReduce): | ≤5S | |
FrequencyRecoveryTime(Sudden Increase): | ≤5S |
Suppliers with verified business licenses